CONTACT US | +55 (11) 4634 - 9000

CONTACT US
+55 (11) 4634 - 9000

Indulink Medium Voltage Cable (8.7/15 kV)

The Indulink medium voltage cable is a type of electrical cable used to transmit electricity at voltages of 8.7/15 kV. It consists of a copper or aluminum conductor insulated with a dielectric material, usually cross-linked polyethylene (XLPE), which guarantees high electrical and thermal resistance.

All information

CABO INDULINK (8,7/15)

ReferênciaCondutor Seção nominal (mm²)Condutor Diâmetro nominal (mm)Isolação Espessura nominal (mm)Isolação Diâmetro nominal (mm)Número de condutoresCobertura Espessura nominal (mm)Cobertura Diâmetro nominal (mm)Peso Total (kg/km)
1330.10.015357,104,517,311,522,9774
1330.30.015357,104,517,332,449,62.970
1330.10.016508,304,518,511,523,9907
1330.30.016508,304,518,532,451,73.424
1330.10.017709,604,519,811,625,61.148
1330.30.017709,604,519,832,655,74.301
1330.10.0189511,34,521,511,627,31.403
1330.30.0189511,34,521,532,759,65.211
1330.10.01912012,74,522,911,728,91.665
1330.30.0191204,522,932,862,96.090
1330.10.02015013,84,524,011,730,01.935
1330.30.0204,524,032,965,87.072
1330.10.02118515,54,525,711,831,92.311
1330.30.0214,525,733,069,78.328
1330.10.02224018,44,528,611,934,62.892
1330.30.0224,528,633,275,510.308
1330.10.02330020,54,530,712,037,33.509
1330.30.0234,530,733,481,312.420
1330.10.02440023,34,533,512,140,34.334
1330.30.0244,533,533,687,815.205
1330.10.02550026,44,536,612,243,65.483
1330.30.0254,536,633,995,119.066

Description



Print information


Certificates

All information

Construction
Applications
Packaging
Specifications
Construction

1.Conductor: Bare electrolytic copper, soft temper, compacted circular stranded (Class 2)

2.Conductor shielding: Semiconductor thermosetting compound.

3. insulation: XLPE 90 °C cross-linked polyethylene thermosetting compound

4.Insulation Shielding: Layer of semiconductor thermosetting compound that is easy to remove when cold.

5.Metallic Shielding: Bare copper wire.

6.Separator: Non-hygroscopic polyester tape, applied in a helix covering 100% of the cable.

7. Cover: PVC ST2 polyvinyl chloride compound.

Cables with 3 conductors, vein identification by means of white, blue and red ribbons.

Applications

INDULINK CABLES are used in input and/or distribution circuits in residential or industrial buildings, substations, etc. They can be installed outdoors, in conduits, ducts, trays or directly underground.

Packaging

They are usually packed in wooden reels

Specifications

ABNT NBR 7287 Power cables with extruded cross-linked polyethylene (XLPE) insulation for voltages from 1 kV to 35 kV – Performance requirements


informações e Tabela


Certificados

CABO INDULINK (8,7/15)

ReferênciaCondutor Seção nominal (mm²)Condutor Diâmetro nominal (mm)Isolação Espessura nominal (mm)Isolação Diâmetro nominal (mm)Número de condutoresCobertura Espessura nominal (mm)Cobertura Diâmetro nominal (mm)Peso Total (kg/km)
1330.10.015357,104,517,311,522,9774
1330.30.015357,104,517,332,449,62.970
1330.10.016508,304,518,511,523,9907
1330.30.016508,304,518,532,451,73.424
1330.10.017709,604,519,811,625,61.148
1330.30.017709,604,519,832,655,74.301
1330.10.0189511,34,521,511,627,31.403
1330.30.0189511,34,521,532,759,65.211
1330.10.01912012,74,522,911,728,91.665
1330.30.0191204,522,932,862,96.090
1330.10.02015013,84,524,011,730,01.935
1330.30.0204,524,032,965,87.072
1330.10.02118515,54,525,711,831,92.311
1330.30.0214,525,733,069,78.328
1330.10.02224018,44,528,611,934,62.892
1330.30.0224,528,633,275,510.308
1330.10.02330020,54,530,712,037,33.509
1330.30.0234,530,733,481,312.420
1330.10.02440023,34,533,512,140,34.334
1330.30.0244,533,533,687,815.205
1330.10.02550026,44,536,612,243,65.483
1330.30.0254,536,633,995,119.066

Solicite o seu orçamento​