CONTACT US | +55 (11) 4634 - 9000

CONTACT US
+55 (11) 4634 - 9000

INDULINK CABLE – Aluminum 138 kV – HIGH VOLTAGE

Indulink cable is a type of high-voltage cable used for transmitting electricity in power distribution systems. Specifically, Indulink cable is made of aluminum and has a voltage rating of 138 kV, which means it is designed to withstand high-voltage electrical currents.

All information

CABO INDULINK – COBRE 138 kV

CONDUTOR SEÇÃO NOMINAL (mm²)CONDUTOR DIÂMETRO NOMINAL (mm)ISOLAÇÃO ESPESSURA NOMINAL (mm)ISOLAÇÃO DIÂMETRO NOMINAL (mm)COBERTURA ESPESSURA NOMINAL (mm)COBERTURA DIÂMETRO NOMINAL (mm)PESO TOTAL (kg/km)
30020,821,667,03,783,66.428
40023,321,669,53,886,36.889
50026,221,672,43,989,47.450
63030,521,676,74,093,98.220
80034,021,680,24,197,69.012
CONDUTOR SEÇÃO NOMINAL (mm²)CONDUTOR DIÂMETRO NOMINAL (mm)ISOLAÇÃO ESPESSURA NOMINAL (mm)ISOLAÇÃO DIÂMETRO NOMINAL (mm)COBERTURA ESPESSURA NOMINAL (mm)COBERTURA DIÂMETRO NOMINAL (mm)PESO TOTAL (kg/km)
30020,521,666,73,783,38.223
40023,321,669,53,886,39.213
50026,421,672,63,989,610.544
63030,521,676,24,093,912.082

Description



Print information


Certificates

All information

Construction
Applications
Specifications
Construction

1. Conductor: Bare electrolytic copper or aluminum, soft tempered, compacted circular stranded (Class 2), blocked against longitudinal water penetration.

2. Conductor shield: Semiconducting thermosetting compound.

3. Insulation: TR XLPE (Tree Retardant) 90° C cross-linked polyethylene thermosetting compound.

4. Insulation shield: Semiconductor thermosetting compound.

5. Insulation banding: Semiconductor tape blocked against longitudinal water penetration.

6. Metallic shielding: Bare copper wires with a section suitable for the project and blocked against longitudinal water penetration.

7. Separator: Semiconductor tape blocked against longitudinal water penetration.

8. Blocking: Polythene aluminum tape (APL) against radial water penetration.

9. Cover: Thermoplastic polyethylene compound PE ST7 (HDPE).

Applications
The INDULINK 69 Kv ~138 kV CABLES are applicable to all public, industrial and utility environments (power generation, transmission and distribution). The cables can be installed in galleries, ducts, directly underground or in
buried or in subfluvial and sublacustrine crossings.
The sizing of high-voltage cables depends on the power to be transmitted, the applicable protections, the environmental and installation conditions (trefoil or apartment formation, natural or forced ventilation, etc.).
Specifications

IEC 60840 – Power Cables with Extruded Insulation for Rated Votages above 30kV (UM = 36kV) up to 150 kV (UM = 170 kV) – Test Methos na Requirements.


informações e Tabela


Certificados

CABO INDULINK – COBRE 138 kV

CONDUTOR SEÇÃO NOMINAL (mm²)CONDUTOR DIÂMETRO NOMINAL (mm)ISOLAÇÃO ESPESSURA NOMINAL (mm)ISOLAÇÃO DIÂMETRO NOMINAL (mm)COBERTURA ESPESSURA NOMINAL (mm)COBERTURA DIÂMETRO NOMINAL (mm)PESO TOTAL (kg/km)
30020,821,667,03,783,66.428
40023,321,669,53,886,36.889
50026,221,672,43,989,47.450
63030,521,676,74,093,98.220
80034,021,680,24,197,69.012

CONDUTOR SEÇÃO NOMINAL (mm²)CONDUTOR DIÂMETRO NOMINAL (mm)ISOLAÇÃO ESPESSURA NOMINAL (mm)ISOLAÇÃO DIÂMETRO NOMINAL (mm)COBERTURA ESPESSURA NOMINAL (mm)COBERTURA DIÂMETRO NOMINAL (mm)PESO TOTAL (kg/km)
30020,521,666,73,783,38.223
40023,321,669,53,886,39.213
50026,421,672,63,989,610.544
63030,521,676,24,093,912.082

Solicite o seu orçamento​