Construction
1. Conductor: Tinned electrolytic copper, soft temper, flexible stranding: class 5.
2. Conductor shielding: Semiconductor thermosetting compound.
3. Insulation: High-modulus HEPR thermoset rubber compound for maximum conductor operating temperature of 90 °C, overload 130 °C and short-circuit 250 °C.
4. Insulation shield: Semiconductor thermosetting compound that is easy to remove when cold
5. Metal shield: Tinned copper wire braid with at least 85 % coverage*.
6. Cover: Thermoplastic polyurethane compound with excellent abrasion, tear and moisture resistance and flexibility properties.
Cover in black
Applications
The Eproflex Jumper 90 Cable is used to maintain the continuity of the power supply in substations during maintenance, replacement of equipment, refurbishment of the substation layout, coupling of emergency generators or any other activity that would require the interruption of the circuit.
Packaging
Wooden reels.
Specifications
The Eproflex Jumper 90 cable meets the requirements of ABNT NBR 7286 – Power cables with extruded ethylene-propylene rubber insulation (EPR, HEPR or EPR 105) for voltages from 1 kV to 35 kV – Performance requirements, where applicable.
informações e Tabela
Certificados
CABO EPROFLEX JUMPER 90 8,7/15 kV
REFERÊNCIA | CONDUTOR SEÇÃO NOMINAL (mm²) | CONDUTOR DIÂMETRO NOMINAL (mm) | ISOLAÇÃO ESPESSURA NOMINAL (mm) | ISOLAÇÃO DIÂMETRO NOMINAL (mm) | COBERTURA ESPESSURA NOMINAL (mm) | COBERTURA DIÂMETRO NOMINAL (mm) | PESO TOTAL |
---|---|---|---|---|---|---|---|
1478.01.014 | 25 | 6,2 | 4,5 | 17,6 | 2 | 24,2 | 822 |
1478.01.015 | 35 | 7,35 | 4,5 | 18,4 | 2 | 24,9 | 922 |
1478.01.016 | 50 | 8,8 | 4,5 | 19,8 | 2 | 26,5 | 1.132 |
1478.01.017 | 70 | 10,4 | 4,5 | 21,4 | 2 | 28,1 | 1.356 |
1478.01.018 | 95 | 12,1 | 4,5 | 23,1 | 2 | 29,6 | 1.573 |
1478.01.019 | 120 | 13,8 | 4,5 | 24,8 | 2 | 31,4 | 1.903 |