INDULINK CABLE – Aluminum 69 kV – HIGH VOLTAGE

CONSTRUCTION

Conductor: aluminium, soft temper, stranded circular compacted (class 2), locked against longitudinal water penetration.
Conductor Shielding: Semiconductor thermosetting compound.
Insulation: Cross-linked polyethylene thermosetting compound TR XLPE (Tree Retardant) 90° C.
Insulation Shielding: Semiconductor thermosetting compound.
Insulation wrapping: Semiconductor tape that blocks longitudinal water penetration.
Metal Shielding: Bare copper wires with section suitable to the project and blocked against longitudinal water penetration.
Separator: Semiconductor tape blocked against longitudinal water penetration.
balao-8 Blocking: Polished aluminium tape (APL) against radial water penetration.
balao-9 Cover: Thermoplastic polyethylene compound PE ST7 (HDPE).
icon-aplicacoes

APPLICATIONS

INDULINK 138 kV aluminum high voltage cables are applicable to all public, industrial and concessionary environments (generation, transmission and distribution of energy). They can be installed in galleries, ducts, directly buried or in under-floor and under-floor crossings.

icon-acondicionamento

CONDITIONING

They are usually packaged in wooden coils.

icon-especificacoes

SPECIFICATIONS

IEC 60840 Power Cables with Extruded Insulation for Rated Votages above 30kV (UM=36 kV) up to 150 kV (UM = 170 kV) – Test Methods an Requirements

icon-impressora

PRINT

Click on the link to generate the PDF for printing or saving to your computer.

 

TABLE

INDULINK CABLE – ALUMINIUM 69 kV

CONDUCTOR - NOMINAL SECTION (mm²)CONDUCTOR - NOMINAL DIAMETER (mm)INSULATION - NOMINAL THICKNESS (mm)INSULATION - NOMINAL DIAMETER (mm)COVER - NOMINAL THICKNESS (mm)COVER - NOMINAL DIAMETER (mm)TOTAL WEIGHT (kg/km)
12013,21136,82,548,52.140
15014,31137,92,649,82.276
18516,31139,92,651,82.467
24018,51142,12,754,22.754
30020,81144,42,856,73.034
40023,31146,92,959,43.394
50026,21149,8362,53.836
63030,51154,13,1674.448