Conductor: Aluminium, soft temper circular compacted stranded (class 2), blocked against longitudinal water penetration. |
![]() |
Conductor Armour: Semiconductor thermosetting compound. |
![]() |
Insulation: Cross-linked polyethylene thermosetting compound, TR XLPE (Tree Retardant) 90° C. |
![]() |
Insulation Shielding: Semiconductor thermosetting compound. |
![]() |
Insulation wrapping: Semiconductor tape that blocks longitudinal water penetration. |
![]() |
Metal Shielding: Bare copper wires with section suitable to the project and blocked against longitudinal water penetration. |
![]() |
Separator: Semiconductor tape blocked against longitudinal water penetration. |
![]() |
Blocking: Polished aluminum tape (APL) against radial water penetration. |
![]() |
Cover: Thermoplastic polyethylene compound PE ST7 (HDPE). |
INDULINK – ALUMINIUM 138 kV CABLE
CONDUCTOR - NOMINAL SECTION (mm²) | CONDUCTOR - NOMINAL DIAMETER (mm) | INSULATION - NOMINAL THICKNESS (mm) | INSULATION - NOMINAL DIAMETER (mm) | COVER - NOMINAL THICKNESS (mm) | COVER - NOMINAL DIAMETER (mm) | TOTAL WEIGHT (kg/km) |
---|---|---|---|---|---|---|
300 | 20,8 | 21,6 | 67,0 | 3,7 | 83,6 | 6.428 |
400 | 23,3 | 21,6 | 69,5 | 3,8 | 86,3 | 6.889 |
500 | 26,2 | 21,6 | 72,4 | 3,9 | 89,4 | 7.450 |
630 | 30,5 | 21,6 | 76,7 | 4,0 | 93,9 | 8.220 |
800 | 34,0 | 21,6 | 80,2 | 4,1 | 97,6 | 9.012 |