FLAME-RESISTANT CABLE – Copper 750 V

CONSTRUCTION

Conductor: Bare electrolytic copper, soft temper, stranded with compact circular section, class 2.
Insulation: 70°C flame retardant thermoplastic compound (PVC).
icon-identificacao

IDENTIFICATION

The ANTICHAMA CABLE is normally produced in the colours black, green and light blue.

icon-aplicacoes

APLICATIONS

ANTICHAMA CABLE is suitable for fixed installations for civil construction at voltages up to 750V. It is usually installed embedded in conduits or gutters and has the property of not allowing the spread of flame.

icon-acondicionamento

PACKAGING

Up to section 16mm² in rolls of 100m. Above 16mm² are packed in coils according to the lengths requested by the customer.

icon-especificacoes

SPECIFICATIONS

NBR NM 247 – Polyvinyl chloride (PVC) insulated cables for rated voltages up to 450/750V.

icon-impressora

PRINT

Click on the link to generate the PDF to print or save to your computer.

icon-certificado

CERTIFICATE

This product is certified. Click on the icon and see the certificate.

TABLE

FIREPROOF CABLE – COPPER 750 V

REFERENCECONDUCTOR - NOMINAL SECTION (mm²)CONDUCTOR - NOMINAL DIAMETER (mm)INSULATION - NOMINAL THICKNESS (mm)INSULATION - NOMINAL DIAMETER (mm)TOTAL WEIGHT (kg/km)
1100.01.01163,10 RN0,84,770
1100.01.012103,80 RC15,8112
1100.01.013164,80 RC16,8162
1100.01.014256,00 RC1,28,4256
1100.01.015357,10 RC1,29,5351
1100.01.016508,10 RC1,410,9473
1100.01.017709,55 RC1,412,4673
1100.01.0189511,30 RC1,614,5907
1100.01.01912012,70 RC1,615,91.130
1100.01.02015013,80 RC1,817,41.395
1100.01.02118515,50 RC219,51.740
1100.01.02224018,00 RC2,222,42.280
1100.01.02330020,50 RC2,425,32.860
1100.01.02440025,30 RN2,630,53.820
1100.01.02550028,60 RN2,834,24.860

RN: Normal Round
CR: Compacted Round