Cable for fixed installations EPROFLEX 90 reduced ground conductor (0,6/1 kV)

  • Cabo eproflex 90 0,6/1kV

CONSTRUCTION

Phase conductors: Electrolytic bare copper, soft temper, flexible stranding.
Insulation: Ethylene Propylene Rubber thermoset compound (HEPR) for 90 °C maximum operation conductor temperature, 130 °C overload and 250 °C short-circuit.
Inner Jacket: Flame retardant polyvinylchloride PVC thermoplastic compound, lead free, applicable to multiconductor cables up to 10 mm².
Overall jacket: Flame retardant polyvinylchloride PVC ST2 thermoplastic compound, lead free, black color.
icon-identificacao

IDENTIFICATION

1 Conductor: Black insulation and black or light blue or green jacket.

2 Conductors: Light blue and black insulation and black jacket.

3 Conductors: Light blue, black and white insulation and black jacket.

4 Conductors: light blue, black, white and red  insulation black jacket.

5 Conductors: light blue, black, white, red and green insulation black jacket.

Cables size 50 mm² or higher are supplied with black phases identified through printed numbers. Other colors upon request.

Multiconductor cables with 3 conductors with reduced ground conductor are supplied in colors light blue, black, white and green, and those of 4 conductors with reduced groud conductor are light blue, black, white, red and green colors.

icon-aplicacoes

Application

Eproflex 90 Cables are applied as feeders or distributiob circudits up to 1 kV. Designed for fixed installation, they can be used in trays, ducts, troughs, racks or directly buried, in dry and wet locations.

icon-acondicionamento

Packing

Usually supplied in wooden reels.

icon-especificacoes

Specifications

ABNT NBR 7286: Power cables with extruded ethylene propylene rubber (EPR, HEPR or EPR 105) insulation for rated voltages from 1 kV up to 35 kV – Performance requirements.

icon-impressora

IMPRIMIR

Clique no link para gerar o PDF para imprimir ou salvar no seu computador.

icon-certificado

CERTIFICADO

Esse produto tem certificação. Clique no ícone e veja o certificado.

TABELA

CABO PARA INSTALAÇÃO FIXA EPROFLEX 90 (0,6/1 kV)
Referência Condutor Isolação Número de Condutores Cobertura Peso total (kg/km)
Seção nominal (mm²) Diâmetro nominal (mm) Espessura nominal (mm) Espessura nominal (mm) Diâmetro Externo (mm)
1451.01.008 1,5 1,49 0,7 1 0,9 4,69 32,1
1451.02.008 2 1 7,78 88,3
1451.03.008 3 1 8,24 103
1451.04.008 4 1 8,99 124
1451.01.009 2,5 1,95 1 0,9 5,15 43,7
1451.02.009 2 1 8,7 120
1451.03.009 3 1 9,24 144
1451.04.009 4 1,1 10,3 179
1451.01.010 4 2,43 1 0,9 5,63 58,2
1451.02.010 2 1,1 9,86 164
1451.03.010 3 1,1 10,5 199
1451.04.010 4 1,1 11,5 244
1451.01.011 6  3,00 1 1 6,4 80,7
1451.02.011 2 1,1 11 217
1451.03.011 3 1,1 11,7 268
1451.04.011 4 1,2 13 338
1451.01.012 10  3,90 1 1 7,3 120
1451.02.012 2 1,2 13 327
1451.03.012 3 1,2 13,8 411
1451.04.012 4 1,2 15,2 513
1451.01.013 16  5,00 1 1 8,4 174
1451.03.013 3 1,3 16,4 592
1451.04.013 4 1,3 18,1 746
1451.01.014 25 6,2 0,9 1 1,1 10,2 269
1451.03.014 3 1,4 20,2 894
1451.04.014 4 1,5 22,5 1.158
1451.01.015 35 7,35 1 1,1 11,4 360
1451.03.015 3 1,5 22,9 1.208
1451.04.015 4 1,6 25,5 1.565
1451.01.016 50 8,8 1 1 1,2 13,2 504
1451.03.016 3 1,6 26,7 1.687
1451.04.016 4 1,7 29,7 2.190
1451.01.017 70 10,4 1,1 1 1,2 15 688
1451.03.017 3 1,8 31 2.334
1451.04.017 4 1,9 34,4 3.032
1451.01.018 95 12,1 1 1,3 16,9 905
1451.03.018 3 1,9 34,8 3.053
1451.04.018 4 2 38,8 3.969
1451.01.019 120 13,8 1,2 1 1,4 19 1.190
1451.03.019 3 3,1 41,3 4.199
1451.04.019 4 3,2 45,7 5.427
1451.01.020 150 15,5 1,4 1 1,4 21,1 1.455
1451.03.020 3 3,3 46,3 5.173
1451.04.020 4 3,4 51,2 6.686
1451.01.021 185 16,8 1,6 1 1,5 23 1.753
1451.03.021 3 3,4 50,1 6.188
1451.04.021 4 3,6 55,7 8.031
1451.01.022 240 19,9 1,7 1 1,6 26,5 2.349
1451.03.022 3 3,6 57,7 8.262
1451.04.022 4 3,8 64,1 10.731
1451.01.023 300 21,4 1,8 1 1,7 28,4 2.774
1451.01.024 400 25,1 2 1 1,8 32,7 3.762
1451.01.025 500 28 2,2 1 1,9 36,2 4.681